3 Phase 4 Wire Wye, use with a three phase star source. Voltage
Input V1 is connected between phases A and neutral. Voltage
Input V2 is connected between phases B and neutral. Voltage
Input V3 is connected between phases C and neutral. Current
Input I1 measures the current in phase A. Current Input I2
measures the current in phase B. Current Input I3 measures
the current in phase C. This hook up gives correct 3 phase
maths function results regardless of any source or load mismatch. The
calculated signals Vab, Vbc, Vca are also available.
|
 |
3 Phase 4 Wire Delta (high leg), use with a three phase delta
source where the center point of one of the phases is earthed
and used as a neutral. Voltage
Input V1 is connected between phases A and neutral. Voltage
Input V2 is connected between phases B and neutral. Voltage
Input V3 is connected between phases C and neutral. Current
Input I1 measures the current in phase A. Current Input I2
measures the current in phase B. Current Input I3 measures
the current in phase C. This hook up gives correct 3 phase
maths function results regardless of any source or voltage mismatch. The
calculated signals Vab, Vbc, Vca are also available.
|
 |
3 Phase 3 Wire Delta (3 element), use with
a three phase delta source. Voltage Input V1 is connected
between phases A and B. Voltage Input V2 is connected between
phases B and C. Voltage Input V3 is connected between phases
C and A. Current Input I1 measures the current in phase A. Current
Input I2 measures the current in phase B. Current Input I3
measures the current in phase C. This hook up gives correct
3 phase maths function results regardless of any source or load
mismatch. Calculated RMS between A and E and between C and
E are also available..
|
 |
3 Phase 3 Wire Wye (with ground), use with a three phase
star source. Voltage Input V1 is connected between phases
A and B. Voltage Input V2 is not used. Voltage Input V3
is connected between phases C and B. Current Input I1 measures
the current in phase A. Current Input I2 is not used. Current
Input I3 measures the current in phase C. This hook up gives
correct 3 phase maths function results ONLY when there are no
other ways for current to flow (vector sum of Ia + Ib + Ic =
0). The calculated signals Vab, Vbc, Vca are also available.
|
 |
3 Phase 3 Wire Wye, use with a three phase star source. Voltage
Input V1 is connected between phases A and B. Voltage Input
V2 is not used. Voltage Input V3 is connected between phases
C and B. Current Input I1 measures the current in phase A. Current
Input I2 is not used. Current Input I3 measures the current
in phase C. This hook up gives correct 3 phase maths function results ONLY when there are
no
other ways for current to flow (vector sum of Ia + Ib + Ic =
0).
|
 |
3 Phase 2.5 Element Wye, use with a three phase star source. Voltage
Input V1 is connected between phase A and neutral. Voltage
Input V2 is not used. Voltage Input V3 is connected between
phase C and neutral. Current Input I1 measures the current
in phase A. Current Input I2 measures the current in phase
B. Current Input I3 measures the current in phase C. This
hook up gives correct 3 phase maths function results ONLY when
the voltages are balanced, i.e. vector sum of (Van + Vbn +
Vcn) = 0.
|
 |
3 Phase 1 Element Wye, use with a three phase star source. Voltage
Input V1 is connected between phase A and Bl. Voltage Input
V2 and V3 are not used. Current Input I1 and I2 are not used. Current
Input I3 measures the current in phase C. This hook up gives
correct 3 phase maths function results ONLY when voltages and
currents are balanced.
|
 |
2 Phase 2 Element Wye, use with a two phase, split phase
source. Voltage Input V1 is connected between phase A and
neutral. Voltage Input V2 is connected between phase B and
neutral. Voltage Input V3 is not used. Current Input I1
measures the current in phase A. Current Input I2 measures
the current in phase B. Current Input I3 is not used. This
hook up gives correct 2 phase maths function results regardless
of any load or source mismatch between phases.
|
 |
Uncommitted, use for non-standard hook ups. No assumptions
are made about the hook up. All power maths functions are available. You must ensure measurement functions
selected are appropriate for the connections made. Harmonic
Direction functions may not be available.
|